No defrost

What is going on

On a system that defrosts with a heated solution, no defrost means the solution is not getting hot enough or is not reaching the coil. Confirm the unit is isolated and locked out before opening any access panels, since these systems combine hot fluid, line voltage and refrigerant. Check what the solution is actually doing before assuming the controls are at fault.

Likely causes

  • Solution not preheated, because the heater or hot-gas heat exchanger has failed
  • Solution pump failed or not moving fluid
  • Liquid solenoid not closing, so the coil keeps getting cold refrigerant
  • Evaporator fans not stopped during defrost

Check in this order

  1. Measure the solution temperature at the tank or sump and compare it with what the manual calls for
  2. If it is cold, check the heater element or the hot-gas heat exchanger supply, with power locked out for any resistance check
  3. Confirm the pump runs and moves fluid, and listen for cavitation or a dry pump
  4. Check the timer outputs to confirm the pump, liquid solenoid and fans each get their signals in the right order
  5. Have a licensed refrigeration technician handle any heat exchanger or refrigerant side work

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.