All brands · General troubleshooting

Monthly check

What is going on

Monthly steam boiler check. Quick, but it saves boilers. Water level, relief and the low water cutoff are what keep a steam boiler from running dry. Hot water and steam can scald, so work with care.

Likely causes

  • Water level too high or too low in the sight glass
  • Relief lever not discharging
  • Low water cutoff not tripping on drain
  • Sediment in the glass or control making readings unreliable

Check in this order

  1. Check the sight glass, it should sit at 1/3 to 1/2.
  2. If it's high, drain some off.
  3. If it's low but visible, add water.
  4. If none is visible or pressure is high, shut it off, let it cool, then add water.
  5. Test the relief lever and confirm it discharges.
  6. Drain to confirm the LWCO trips.
  7. Hot water and steam can scald, so work with care.

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.