All brands · General troubleshooting

Moisture indicator shows wet

What is going on

Moisture indicator reads wet. Don't ignore it. Water in the system makes acid and freezes at the metering device. Take the reading under the right conditions first, since a hot line can fool you.

Likely causes

  • Moisture in the system from a leak, poor evacuation, or a saturated drier that's too small
  • Alcohol additive in the system
  • Reading taken on a hot liquid line, which can mislead the other way

Check in this order

  1. Take the reading with the liquid line near 75°F
  2. Replace the drier and never reuse the old one
  3. Re-check the indicator after the system runs a while
  4. Indicator turns tan that's oil, not moisture. Flush it out.
  5. If tan keeps coming back, there is too much oil circulating, so check oil level and return
  6. If it stays wet after a new drier, find the leak or redo the evacuation

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.