Leak check false alarms near foam insulation
What is going on
If your leak detector keeps going off near foam insulation, don't assume you have found a leak. The blowing agent in urethane foam can set off both halide torches and electronic detectors, so you get false alarms right where you are looking. It is a common trap on insulated cabinets and panels.
Likely causes
- Urethane foam blowing agent giving off vapor that triggers halide torches and electronic detectors
Check in this order
- Switch to bubble solution in that area, since it only reacts to a real leak
- Brush it on the joints and watch for bubbles building
- Keep the detector for areas away from the foam
- Pressure test the circuit if you are still unsure
More general guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.