Draft complaints

What is going on

Draft complaints are almost always an air-velocity or distribution issue, not a sign the equipment is broken. Before changing anything, find where the air is coming from and how fast it is moving at the register, since people feel anything much over about 500 fpm as a draft.

Likely causes

  • Register velocity over 500 fpm at the occupied zone
  • Unbalanced system sending too much air one place and too little elsewhere
  • Too much air delivered to one room

Check in this order

  1. Check the airflow with a smoke pencil to see where it travels, and measure it with an anemometer. Confirm the number before you decide anything
  2. Redirect the louvers away from where people sit
  3. Swap in a broader-diffusing register to slow and spread the air
  4. Partly close the branch damper for that room
  5. Rebalance the whole system once the high spots are corrected, and recheck the comfort afterward

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.