Defrost ineffective or too slow; drain refreezes

What is going on

If a defrost seems weak or slow and the drain freezes up again, the coil is not getting enough heat for long enough, or the water cannot leave. On hot-gas systems, that usually comes down to the solenoid, the compressor and fan sequence, or the valve that sets defrost pressure. Walk the sequence in order and you will find where heat is getting lost.

Likely causes

  • Hot-gas solenoid not opening, so no heat gets to the coil
  • Compressor not running during defrost, so there is no hot gas to send
  • Evaporator fans not stopped, which blows heat away from the coil
  • Drain not heated, so meltwater refreezes
  • Low-pressure-adjusting valve miscalibrated and holding the wrong defrost pressure

Check in this order

  1. Check the solenoid coil for voltage and continuity, then confirm the valve actually lifts and passes gas
  2. Look at the timer contacts that control the compressor and the fans during defrost
  3. Calibrate the pressure-adjusting valve using the manufacturer table for your refrigerant
  4. Confirm the drain pan and drain line heat is working
  5. Watch a full defrost and take coil and drain temperatures to see where heat stops

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.