Midea · Furnace troubleshooting

Resetting a locked-out furnace

What is going on

How to clear a lockout after ignition failure on the BGH96M control.

Likely causes

  • Ignition not achieved after repeated attempts

Check in this order

  1. Read and note the diagnostic LED code before resetting.
  2. Option 1 wait - the control automatically resets after 1 hour.
  3. Option 2 interrupt 115 V power to the furnace for 1-20 seconds.
  4. Option 3 lower the thermostat to remove the call for heat for 1-20 seconds.
  5. If it locks out again, troubleshoot the code shown (E7/E8 etc.).

Applies to: Midea BGH96M 96% AFUE two-stage gas furnaces (060B3A, 080B3A, 080C4A, 100C5A, 100D5A, 120D5A)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Midea 96% AFUE Gas Furnace (A2L) Troubleshooting Guide, Section 2.2 Resetting From Lockout, p.6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.