Midea · Furnace troubleshooting
Resetting a locked-out furnace
What is going on
If a Midea BGH96M furnace tries to light a few times and fails, the control locks out to protect itself. This covers the 96% AFUE two-stage models (060B3A, 080B3A, 080C4A, 100C5A, 100D5A, 120D5A). A reset gets the homeowner heat again, but a lockout is a symptom, so read the diagnostic LED code first and find out why the furnace could not light.
Likely causes
- Ignition not achieved after repeated attempts, which can come from a dirty flame sensor, weak igniter, gas supply problem or a vent or pressure switch issue
Check in this order
- Read and note the diagnostic LED code before you reset anything, so the clue is not lost.
- Option 1 just wait. The control automatically resets after 1 hour.
- Option 2 interrupt 115 V power to the furnace for 1 to 20 seconds, using the service switch or breaker.
- Option 3 lower the thermostat to remove the call for heat for 1 to 20 seconds.
- If it locks out again, troubleshoot the code shown (E7, E8 and so on) and do not keep resetting it. Gas and ignition faults call for a licensed technician.
Applies to: Midea BGH96M 96% AFUE two-stage gas furnaces (060B3A, 080B3A, 080C4A, 100C5A, 100D5A, 120D5A)
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Midea 96% AFUE Gas Furnace (A2L) Troubleshooting Guide, Section 2.2 Resetting From Lockout, p.6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.