Midea · Furnace troubleshooting

No light and no fan - furnace does not start

What is going on

Furnace shows no LED activity and the blower does not run on a call for heat or fan.

Likely causes

  • No 115 V power to the furnace
  • Blower door switch open or door not closed
  • Blown fuse
  • Failed transformer
  • Thermostat not sending a call
  • Loose/wrong wiring
  • Blower motor or fan drive board failure
  • Control board failure

Check in this order

  1. Warning: Discharge static before touching the control board; disconnect power before handling wiring.
  2. Check for 115 VAC between L1 and common at the furnace; if missing, check the supply at the connection box/disconnect.
  3. Make sure the blower access door is closed properly; with power off, press in the door switch and confirm 0 ohms. Replace the door switch if open.
  4. Check the board fuse; replace if blown. If the fuse is good, check the transformer secondary for 18-31 VAC and replace the transformer if it is dead.
  5. Check for 18-31 VAC between R and C; then check W/W1 to C (heating call) and G to C (fan call). No call = check thermostat settings or replace the thermostat.
  6. Check for loose wires or wrong connections and correct per the wiring diagram; leave the PARK terminal unused.
  7. If the board receives the call but nothing happens, check for 18-31 VAC between the speed tap (hi-heat/lo-heat/hi-cool/lo-cool) and COM and 115 VAC between CIRC-H and N. Replace the board if outputs are missing.
  8. If the motor gets signal and power but does not turn, measure resistance between motor leads U, V and W (should be 2-10 ohms). If in range, replace the fan drive board; if not, replace the motor.

Applies to: Midea BGH96M 96% AFUE two-stage gas furnaces (060B3A, 080B3A, 080C4A, 100C5A, 100D5A, 120D5A)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Midea 96% AFUE Gas Furnace (A2L) Troubleshooting Guide, Section 3.1 chart and Figs. 1-8, p.7-9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.