Single phasing (one fuse/breaker open)

What is going on

Motor runs hot and may burn out; the phase-loss monitor trips. One leg of the three-phase supply is missing because a fuse or breaker pole is open.

Likely causes

  • One fuse or breaker open, so the motor is running on two phases
  • Loose or burnt connection on one leg
  • Open winding inside the motor

Check in this order

  1. Turn power off and lock out before opening any terminal box
  2. Measure voltage on each of the three legs at the motor terminals, with power on only for the readings and by a qualified person
  3. A wrong or missing leg points to the power supply or a fuse
  4. If all three legs are correct, power off and ohm each winding set
  5. Unequal readings mean a shorted or open winding, so service or replace the motor
  6. Do not keep resetting a monitor that keeps tripping

More electrical guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.