All brands · Electrical troubleshooting

Element overheats/burns open

What is going on

An element that keeps burning open is almost always starved for air. The airflow safety switch closes too early or the element sits in dead air, and it cooks itself. If a manual-reset limit or fusible link has opened, something made it get that hot, so find the reason and do not just replace the part.

Likely causes

  • Airflow below minimum, so the switch closes too early
  • Blocked ducts or registers, or a failed blower
  • Manual-reset limit or fusible link opened, which means there was an overheat to track down

Check in this order

  1. Shut off power at the breaker and confirm it is dead before opening the furnace
  2. Check the filter, registers and duct dampers for blockage
  3. Confirm the blower runs at the right speed and moves air
  4. Inspect the element and limit for the cause of the overheat
  5. Replace the blown element, limit or fusible link with the correct part
  6. Retest with a temperature rise check and make sure the element does not cycle on the limit

More electrical guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.