All brands · Electrical troubleshooting

Any circuit fault — classify the problem

What is going on

Every electrical complaint, whether a dead load, a tripping breaker, a blown fuse, a shock or low voltage at the unit, comes down to one of five circuit faults. Name which one you have and the meter tests get a lot shorter. Work with power off and locked out when you measure resistance, and treat live voltage checks with respect.

Likely causes

  • Short circuit
  • Ground fault
  • Overload
  • Unintentional voltage drop
  • Open circuit

Check in this order

  1. Short means instant trip, with near-zero resistance around the load. Check with power off.
  2. Ground fault means energized metal, a GFCI that trips, and ohms from hot to ground.
  3. Overload is current above rating following the normal path, so the breaker trips slowly or not at all. Look for too many parallel loads, wrong supply, strained equipment or a failing component.
  4. Voltage drop shows when voltage at the panel and at the unit differ by more than plus or minus 10 percent. Suspect long or undersized wire, poor connections or bad contacts.
  5. Open means full applied voltage across the component and zero amps. Look for a broken wire, blown fuse or breaker, burnt component or bad connection.
  6. Clamp the amps and compare with the nameplate to separate overload from open.
  7. If you find damaged insulation or burnt wiring, shut the circuit off and bring in a licensed electrician.

More electrical guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.