All brands · Electrical troubleshooting
Fuse blows / breaker trips repeatedly
What is going on
A fuse that blows or a breaker that trips over and over is telling you something, and the thing I usually find first is the wrong fuse in the holder. A fast-acting fuse on a compressor will pop on every start because of the inrush. After that it is a short, or the motor is overloaded. Don't just keep putting bigger fuses in.
Likely causes
- Wrong fuse rating or type for the motor, such as a fast-acting fuse on a compressor
- Short in the circuit
- Motor overload
Check in this order
- Turn the power off and lock it out before you touch anything
- Confirm the rating against the motor fuse table (A21) and the UL nameplate
- Use time-delay fuses on compressors
- If the rating is correct, hunt for a short with a meter
- On a breaker, examine its capacity; if it is adequate, there is a short or other trouble
- For anything beyond simple checks, call a licensed electrician or technician
More electrical guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.