All brands · Electrical troubleshooting
Reads 24 V or less / transformer failing
What is going on
What I usually find when a control transformer reads 24 volts or less is not the transformer at all, it's what got hung on it. Add-on humidifiers, air cleaners and zone panels wired off the furnace transformer pile on load until it sags. An old transformer can fail too, but check the loads before you condemn it. A low reading under load is the clue. A good one should hold at or slightly above 24 volts.
Likely causes
- Aging transformer that sags under load
- Series loads dropping voltage
- Too many parallel loads, such as add-on humidifiers, air cleaners and zone panels wired off the furnace transformer
- A load drawing over nameplate, such as contactors, time delays, fan relays, liquid solenoids, gas valves, zone dampers or valves, ignition controls, oil primaries and stats
- A chattering relay or contactor pulling the voltage down
Check in this order
- Trace the circuit and build a ladder diagram so you know every load on it.
- Remove any series load, since it steals voltage.
- Sum load amps times 24 V. If it is more than the transformer VA, upsize the transformer.
- Clamp each branch with the 10-wrap trick, wrapping the wire ten times around the clamp and dividing the reading by ten.
- Replace any load over its rating.
- Listen for chattering from relays and contactors.
- Recheck the secondary voltage with everything calling.
- Shut off power before you replace any load or the transformer.
More electrical guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.