Motor dead with proper voltage
What is going on
If you have the right voltage at the motor terminals and the motor still will not turn or even hum, the problem is inside the motor circuit. That usually means a bad motor, an overload that has opened, or a run capacitor that has failed. It is a pretty common call and an easy one once you meter it step by step.
Likely causes
- Open motor winding
- Open overload protector
- Shorted or open run capacitor
Check in this order
- Turn the power off and check that the motor shaft spins freely by hand
- Meter the winding resistance between motor leads and look for an open
- Check the overload, since many reset after cooling, and note why it tripped
- Discharge the capacitor safely, then test with a meter that reads capacitance and compare to the rating on the can
- Check for a short to ground on the windings
- Replace the motor or capacitor and match the rating plate
More electrical guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.