NTI · Boiler troubleshooting

Outdoor temperature alert (Alert 248)

Trinity Tft

What is going on

Controller expects an outdoor sensor because outdoor reset is on from the factory.

Likely causes

  • Sensor not connected
  • Wiring on wrong terminals
  • Faulty or iced-up sensor

Check in this order

  1. Connect the outdoor sensor or switch outdoor reset off
  2. Wires belong on OUTDOOR and COM
  3. Check the sensor is free of ice and snow and compare resistance with the thermistor chart

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.