NTI · Boiler troubleshooting
Boiler bangs or hisses; Lockout 81 delta T
What is going on
Noise and delta-T trips usually mean not enough water flow.
Likely causes
- Insufficient flow
- Scaled or magnetite-coated heat exchanger
- Low system pressure
Check in this order
- Check fuse B and the boiler pump
- Confirm piping matches the piping section and pressure is at least 15 PSI
- Descale the heat exchanger with Fernox DS-40 if scaled
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
More boiler guides
Related
NTI error codes · NTI parts · NTI tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.