NTI · Boiler troubleshooting

Low water cutoff / ILK OFF lockout (67)

Trinity Tft

What is going on

Burner will not fire and display reads ILK OFF.

Likely causes

  • Low water in boiler
  • External limit open
  • Condensate blockage switch open

Check in this order

  1. Check water level and the internal low water cutoff
  2. Check any external limit wired between R and LIM
  3. Clean the condensate trap and drain and check the vent, then clear the lockout; if still open, test the condensate switch contacts 1 and 2 for continuity

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.