Display shows System Disconnected! constantly

Trinity Tft

What is going on

Display is powered but cannot talk to the controller.

Likely causes

  • Communication wire off
  • Blown 24 VAC fuse C
  • Failed 24 VAC transformer
  • Control board dead

Check in this order

  1. Check the 4 by 1 Molex connector behind the top of the display is seated
  2. Check the wires on the back of the display: green, red and black to terminals 1, 2 and 3
  3. Check fuse C
  4. Look at the power LED on the control and measure 24 VAC at J8 pins 1 and 2
  5. If 24 VAC is present, make sure plug J8 is seated, cycle power, and replace the control if it still does not run

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.