NTI · Boiler troubleshooting

Burner not running on a call for heat

Trinity Tft

What is going on

Heat call present but the boiler is not firing.

Likely causes

  • Demand already satisfied
  • Outlet temperature above setpoint minus on-hysteresis
  • A hold, delay or lockout is active
  • Burner switch is off in the controller
  • Safety setting changed and not yet verified (Lockout 2)

Check in this order

  1. Check Demand and setpoints on the touchscreen
  2. Check thermostat and DHW aquastat settings
  3. Read the Summary page for any Hold, Delay or Lockout code
  4. If Demand says burner switch off, go to the diagnostics burner test page and turn it on
  5. For Lockout 2 complete the safety data verification

Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.