Daikin · Air conditioner troubleshooting

Testing the run capacitor

Daikin R-32 DC3S/DC4S/DC5S

What is going on

Three ways to check a run capacitor.

Check in this order

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Discharge the capacitor through a 200-300 ohm resistor before handling.
  3. Ohm test set the meter to at least 1k ohm, touch the terminals. A good cap shows a reading for a moment then goes back to OL. No change = dead.
  4. Capacitance test take it out of the circuit, read it in capacitance mode. Close to the printed value (may read a bit low) = good. Much lower or nothing = replace.
  5. Under load read the amps on the wire from HERM to the compressor start terminal, multiply by 2,652, divide by the voltage between HERM and C. Compare the result to the printed MFD and its tolerance.

Applies to: DC3SQN, DC4SQA, DC4SEA, DC5SEA (single stage R-32 condensing units with CoreSense module)

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Checking Capacitor p.23-24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.