Daikin · Air conditioner troubleshooting
No cooling: condensing unit check order
What is going on
Work through power, control voltage and the compressor circuit when the AC will not cool.
Check in this order
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Check for 230 V at the unit. No voltage: check breakers and fuses.
- Check 230 V at the transformer and 24 V out of it. Fix wiring or replace the transformer.
- Check 24 V on Y from the thermostat and 24 V at the contactor coil. If missing, check the thermostat, its wiring and the pressure switches.
- Contactor not pulling in with 24 V on the coil: replace the contactor.
- Compressor not running with the contactor closed: check wiring to the compressor, then the run capacitor.
- Compressor warm and overload open let it cool and see if it restarts. Open windings or no restart: replace the compressor.
- Compressor runs but does not pump replace the compressor.
- Indoor blower not running check voltage to the motor and 24 V on G from the thermostat.
- Everything runs but cooling is poor check the charge with subcooling and superheat, and look for a clogged piston or bad TXV.
Applies to: DC3SQN, DC4SQA, DC4SEA, DC5SEA (single stage R-32 condensing units with CoreSense module)
More air conditioner guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Condenser - Cooling p.48. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.