Daikin · Air conditioner troubleshooting

FIT communication error: network check

Daikin FIT DC6VS/DC9VSA

What is going on

Steps to clear a network communication code on a FIT system.

Likely causes

  • Miswired terminal 1 / 2
  • Damaged or broken communication cable
  • Wrong termination for the cable run

Check in this order

  1. Kill power at the disconnect before opening the control box or touching wiring.
  2. Check the low voltage wiring against the install instructions. Terminals 1 and 2 swapped is the common mistake.
  3. Look for broken wires at terminals and inside wire nuts, and damage on the cable between units.
  4. Do a continuity check on each wire. Replace the cable if needed.
  5. Do not land more than two wires on one terminal; they come loose.
  6. Try the termination dip switch combinations: DS1 (switches 1 and 2) on the outdoor board and DS7 on the indoor board if it has one. Factory setting is both ON on both boards. Try the four combinations one at a time and power up after each change.
  7. Press LEARN about 5 seconds to reset the network.
  8. Read the red and green network LEDs on the boards to narrow it down.

Applies to: DC6VS***1*A*, DC9VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

More air conditioner guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit installation & service reference, Network Troubleshooting p.47 (printed page). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.