Viessmann · Mini-split
ODU P6 Inverter module (IPM) fault (outdoor board)
What the control is telling you
Outdoor board display. Indoor shows PC00 (old P0).
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Check the supply is 208-230 V, 1 phase, 60 Hz and the power leads are tight.
- Measure DC across P and N on the IPM 277-356 V on 18-27K units, 277-410 V on 36-48K units.
- Check the cable between the main board and the IPM, the compressor leads, and every terminal in the electrical box.
- Check the bridge rectifier (no terminal pair should read 0 ohms) and each reactor lead for an open.
- Make sure the outdoor fan runs and the unit can breathe. If the fan is the problem, follow the fan fault (EC07).
- Check compressor winding resistance (should be equal on all three pairs).
- Replace in this order and retest each time: IPM module, outdoor main board, compressor.
Models that show this code
7 models in Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor
Other codes on the same units
- ODU P0 Compressor top overheat (outdoor board)
- ODU P1 High pressure protection (outdoor board)
- ODU P2 Low pressure protection (outdoor board)
- ODU P3 Current overload (outdoor board)
- ODU P4 Discharge temperature protection (outdoor board)
- ODU P5 Condenser high temperature (outdoor board)
- ODU PH Compressor pre-heat
- ODU RO Oil return cycle
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 27 Outdoor Unit Digital Codes p.32; diagnosis p.68. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.