Viessmann · Mini-split
ODU P3 Current overload (outdoor board)
What the control is telling you
Outdoor board display. Indoor shows PC08 (old F0).
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Test and repair steps
- Safety kill power at the disconnect and wait for the inverter capacitors to discharge before touching boards or wiring.
- Measure the input current on the supply wire. Limits: 15 A on 18K; 18.5 A on 27K and 18K high heat; 22.5 A on 36K and 27K high heat; 28 A on 48K and 36K high heat.
- Outdoor air above 122 F (50 C) = outside the range, shut it down.
- Check outdoor airflow and clean the coil.
- Check for a refrigerant restriction. If blocked: recover the charge, blow the lines through with nitrogen, evacuate and recharge.
- If none of the above, replace the outdoor main board (or the electric control box) and retest.
Models that show this code
7 models in Viessmann Vitocal 200-S DLCM(R/H)B multi-zone outdoor
Other codes on the same units
- ODU LP Low outdoor temperature protection (outdoor board)
- ODU P0 Compressor top overheat (outdoor board)
- ODU P1 High pressure protection (outdoor board)
- ODU P2 Low pressure protection (outdoor board)
- ODU P4 Discharge temperature protection (outdoor board)
- ODU P5 Condenser high temperature (outdoor board)
- ODU P6 Inverter module (IPM) fault (outdoor board)
- ODU PH Compressor pre-heat
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Table 27 Outdoor Unit Digital Codes p.32; diagnosis p.64-65. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.