Viessmann · Mini-split

EC 50 Temperature sensor fault (listed in diagnosis heading only)

Medium severity Vitocal 100-SDLCURA

What the control is telling you

Sensor fault in the temperature sensor group. Sampling voltage below 0.06 V or above 4.94 V. Not in the Table 8 error list.

Applies to: DLCURA 18-60 outdoor unit

Likely causes

  • Sensor wiring open or shorted
  • Faulty sensor
  • Faulty outdoor PCB

Test and repair steps

  1. Check the connection between the sensor and the PCB.
  2. Make sure the wiring is correct.
  3. Measure the sensor resistance.
  4. Replace the sensor if it is outside acceptable values.
  5. Replace the outdoor PCB if the fault remains.

Models that show this code

22 models in Vitocal 100-S, DLCURA

36AAK48AAK58AAK80ES(N,L)80ESUDLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABKFEM4FVM4X48***LFVM4X60***LFXM4X48**ALFXM4X60**AL

Other codes on the same units

  • EC 57 Refrigerant pipe temperature sensor fault
  • EC 5C High pressure sensor fault
  • EC 71 Outdoor DC fan motor overcurrent failure
  • EC 72 Outdoor DC fan motor lack of phase failure
  • EC 73 Outdoor DC fan motor zero-speed failure
  • EL 16 Adapter board to outdoor main board communication malfunction
  • LC 06 IPM module high temperature protection
  • PC 06 Compressor discharge temperature protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann DLCURA service manual, p. 29 (diagnosis heading). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.