EC 51 Outdoor unit EEPROM parameter error

High severity Vitocal IND-F

What the control is telling you

Outdoor PCB main chip does not receive feedback from the EEPROM chip. Compressor-driver EEPROM and communication errors between outdoor main chip and compressor driver follow the same procedure.

Applies to: Outdoor unit

Likely causes

  • EEPROM on outdoor PCB not responding to main chip

Test and repair steps

  1. Shut off power, wait 2 minutes, then turn power back on.
  2. If the code returns, replace the outdoor main PCB (F4).
  3. On models where the outdoor PCB cannot be removed, replace the whole outdoor electric control box.

Other codes on the same units

  • EC Refrigerant leakage detected
  • EC 07 Outdoor fan speed out of normal range
  • EC 0d Outdoor unit malfunction
  • EC 52 Condenser coil temperature sensor T3 fault
  • EC 53 Outdoor room temperature sensor T4 fault
  • EC 54 Compressor discharge temperature sensor TP fault
  • EC 55 IGBT temperature sensor TH fault
  • EC 56 Evaporator coil outlet temperature sensor T2B fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitocal IND-F DLFSFBH service manual, p. 15-16. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.