Viessmann · Mini-split
EC 5C High pressure sensor fault
What the control is telling you
High pressure sensor is open or shorted. Sampling voltage below 0.06 V or above 4.94 V.
Applies to: DLCURA 18-60 outdoor unit
Likely causes
- Sensor wiring open or shorted
- Faulty sensor
- Faulty outdoor PCB
Test and repair steps
- Check the connection between the sensor and the PCB.
- Make sure the wiring is correct.
- Measure the sensor resistance.
- Replace the sensor if it is outside acceptable values.
- Replace the outdoor PCB if the fault remains.
Models that show this code
22 models in Vitocal 100-S, DLCURA
Other codes on the same units
- EC 50 Temperature sensor fault (listed in diagnosis heading only)
- EC 57 Refrigerant pipe temperature sensor fault
- EC 71 Outdoor DC fan motor overcurrent failure
- EC 72 Outdoor DC fan motor lack of phase failure
- EC 73 Outdoor DC fan motor zero-speed failure
- EL 16 Adapter board to outdoor main board communication malfunction
- LC 06 IPM module high temperature protection
- PC 06 Compressor discharge temperature protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann DLCURA service manual, p. 25 (table p. 29; diagnosis p. 29). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.