Viessmann · Mini-split

EC 73 Outdoor DC fan motor zero-speed failure

High severity Vitocal 100-SDLCURA

What the control is telling you

Outdoor DC fan motor reads zero speed.

Applies to: DLCURA 18-60 outdoor unit

Likely causes

  • Faulty fan motor
  • Fan assembly obstructed or hard to turn
  • Wiring or connection fault
  • Faulty outdoor PCB

Test and repair steps

  1. Shut off power, wait 2 minutes, then restart the unit.
  2. If the fault remains, shut off power and turn the fan by hand.
  3. If the fan does not turn easily, find and remove the cause.
  4. If the fan turns easily, check the fan motor wiring and make sure connections are correct.
  5. Measure the fan motor voltage from the PCB.
  6. Replace the main PCB if the voltage is wrong.
  7. Release the UVW connector and measure U-V, U-W and V-W resistance. If unequal, replace the fan motor; if equal, replace the PCB.
  8. Replace the fan motor if the problem persists.

Models that show this code

22 models in Vitocal 100-S, DLCURA

36AAK48AAK58AAK80ES(N,L)80ESUDLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABKFEM4FVM4X48***LFVM4X60***LFXM4X48**ALFXM4X60**AL

Other codes on the same units

  • EC 50 Temperature sensor fault (listed in diagnosis heading only)
  • EC 57 Refrigerant pipe temperature sensor fault
  • EC 5C High pressure sensor fault
  • EC 71 Outdoor DC fan motor overcurrent failure
  • EC 72 Outdoor DC fan motor lack of phase failure
  • EL 16 Adapter board to outdoor main board communication malfunction
  • LC 06 IPM module high temperature protection
  • PC 06 Compressor discharge temperature protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann DLCURA service manual, p. 27 (diagnosis p. 27; fan motor check p. 28). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.