Viessmann · Heat pump
EH 62 Open or short circuit of temperature sensor
What the control is telling you
The sensor sampling voltage is below 0.06 V or above 4.94 V. The LED shows the failure.
Applies to: DLCLRC outdoor units 36, 48, 58
Likely causes
- Broken or shorted sensor wiring
- Poor connection between sensor and PCB
- Failed sensor
- Failed indoor or outdoor PCB
Test and repair steps
- Check the connection between the temperature sensor and the PCB.
- Make sure the sensor is wired properly and the connections are secure.
- Measure the sensor resistance. If it is out of range, replace the sensor.
- If the sensor and wiring are good, replace the indoor PCB (E4/E5) or outdoor PCB (F1/F2/F3).
- On some models the outdoor PCB cannot be removed alone. Replace the whole outdoor electric control box.
Models that show this code
22 models in Vitocal 100-S
Other codes on the same units
- PH91 Low temperature protection of evaporator
- DF Defrost display (normal)
- EC 72 Missing phase failure of outdoor DC fan motor
- EH 65 Open or short circuit of temperature sensor
- EL 16 Communication malfunction between adapter board and outdoor main board
- FC FC display (normal)
- FL 09 Indoor and outdoor unit mismatch
- LC 06 IPM module high temperature protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLCLRC Service Manual, p. 25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.