Viessmann · Heat pump

EC 72 Missing phase failure of outdoor DC fan motor

High severity Vitocal 100-SDLCURA

What the control is telling you

The three-phase sampling current of the DC fan motor is abnormal. One or more phases stay very low, close to 0.

Applies to: DLCURA outdoor units, models 18AAK to 60ABK

Likely causes

  • Open circuit in fan motor three-phase output
  • Loose or bad fan motor wiring
  • Unequal or open fan motor windings
  • Faulty fan motor
  • Faulty outdoor PCB

Test and repair steps

  1. Check the fan three-phase output for an obvious open circuit.
  2. Power off, then restart the unit 2 minutes later and check whether the code returns.
  3. Check the fan motor wiring and correct any bad connections.
  4. Measure the motor winding resistance. All windings should read nearly equal.
  5. Replace the fan motor if the windings are unequal or open.
  6. Replace the main PCB if the fault remains.

Models that show this code

22 models in Vitocal 100-S, DLCURA

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Other codes on the same units

  • PC46 Compressor speed out of control
  • PC49 Compressor overcurrent failure
  • PH90 High temperature protection of evaporator
  • PH91 Low temperature protection of evaporator
  • DF Defrost display (normal)
  • EH 62 Open or short circuit of temperature sensor
  • EH 65 Open or short circuit of temperature sensor
  • EL 16 Communication malfunction between adapter board and outdoor main board

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocal 100-S DLCURA service manual, PDF p. 47. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.