E715 Main board communication failure
What the control is telling you
Communication between the main board and the display has failed.
Applies to: Outdoor unit
Likely causes
- Incorrect connection or poor contact
- Display damaged
- Communication line damaged
- Main board communication port damaged
Test and repair steps
- Check connections between main board, terminal block and display.
- Swap in a known good display. If the fault clears, the display is damaged.
- Connect the display directly to the main board. If the fault clears, replace the communication line.
- At power-up, measure voltage change between A and B on the main board. If there is almost no change or it stays near 0.1 V, replace the main board.
Other codes on the same units
- E615 Communication failure (main board with fan motor 2 module board)
- E710 AC input over current shutdown
- E711 Input voltage sampling fault
- E712 DSP and PFC communication failure
- E713 Drive plate temperature fault
- E714 DSP and communication board communication failure
- E810 - E815 Reserved
- E910 - E912 Reserved
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 83. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.