Viessmann · Heat pump

E711 Input voltage sampling fault

Medium severity Vitocal 100-AW AM2V

What the control is telling you

The input voltage sampling has failed, from abnormal input voltage or a damaged voltage sampling circuit.

Applies to: Outdoor unit

Likely causes

  • Abnormal input voltage
  • Voltage sampling circuit damaged

Test and repair steps

  1. Check whether the input voltage is too low.
  2. If readings are normal and the fault returns after power-off, power-on and restart, replace the driver board.
  3. Fix the grid problem before restarting.
  4. Replace the inverter board if the fault remains after restarting.

Other codes on the same units

  • E614 Reserved
  • E615 Communication failure (main board with fan motor 2 module board)
  • E710 AC input over current shutdown
  • E712 DSP and PFC communication failure
  • E713 Drive plate temperature fault
  • E714 DSP and communication board communication failure
  • E715 Main board communication failure
  • E810 - E815 Reserved

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 83. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.