E615 Communication failure (main board with fan motor 2 module board)
What the control is telling you
Communication between the main board and the fan motor 2 module board has failed.
Applies to: Outdoor unit
Likely causes
- Incorrect connection or poor contact
- Communication line damaged
- Main board communication port damaged
- Fan speed driver board damaged
Test and repair steps
- Check connections between main board, terminal block and display.
- Connect the fan board directly to the main board. If the fault clears, replace the communication line.
- At power-up, measure voltage change between A and B on the main board. If there is almost no change or it stays near 0.1 V, replace the main board.
- If everything else is OK, replace the fan speed driver board.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 81. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.