FD 227 Boiler coding card missing (with B7)
What the control is telling you
Burner in fault state; additional fault B7 is displayed. Detailed code 227.
Applies to: Vitodens 200-W B2HA 45, 60
Likely causes
- Boiler coding card missing
Test and repair steps
- Insert the boiler coding card.
- Press reset button R.
- Replace the control unit if the fault persists.
Other codes on the same units
- EE 132 Flame signal missing or weak at burner start
- EF 138 Flame lost during safety time
- FA 154 Fan not at standstill
- FC 190 Gas valve or modulation valve control fault, or vent blocked
- FD (unnamed row) Burner control unit fault (EMC)
- FE 158, 159, 162 or 225 Damaged or wrong boiler coding card or main PCB
- FF 224 Internal fault or reset button blocked
- OFF OFF displayed: heating program off
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Vitodens 200-W B2HA 45, 60 Service Instructions, p. 77. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.