Viessmann · Boiler
F.68 Flame signal present at burner start
What the control is telling you
Burner in a fault state; a flame signal exists before ignition.
Applies to: Vitodens 200-W B2HE 85, 120, 150, 199
Likely causes
- Stray ionization signal
- Faulty BCU
Test and repair steps
- Close the gas shut-off valve.
- Disconnect the ionization electrode cable.
- Reset the appliance.
- If the fault stays, replace the BCU burner control unit.
Models that show this code
3 models in Vitodens 200-W B2HE
Other codes on the same units
- F.669 DHW reheating sensor TS4 short circuit
- F.67 Ionization current outside permitted range
- F.670 Buffer sensor TS3 open circuit
- F.671 Buffer sensor TS3 short circuit
- F.672 Thermostat-function sensor TS3 open circuit
- F.673 Thermostat-function sensor TS3 short circuit
- F.69 Ionization current outside permitted range (valve/electrode check)
- F.691 No combustion air supply feedback
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.