Viessmann · Boiler

F.14 Outside temperature sensor short circuit

Low severity Vitodens 200-W B2HE

What the control is telling you

Control behaves as if outside temperature were 0 C (32 F).

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Shorted outside sensor or wiring

Test and repair steps

  1. Check the outside sensor and its connection (external plug, contacts 1 and 2).
  2. Replace the faulty part.

Models that show this code

3 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-85

Other codes on the same units

  • F.11 Solar collector sensor open circuit
  • F.12 Solar collector sensor short circuit
  • F.13 Outside temperature sensor open circuit
  • F.142 CAN bus communication error
  • F.143 Fan overheating (air mass flow sensor / recirculation)
  • F.15 Storage tank sensor open circuit (solar/backup)
  • F.16 Storage tank sensor short circuit (solar/backup)
  • F.160 CAN bus communication error (external/internal)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.