Viessmann · Boiler

F.12 Solar collector sensor short circuit

Low severity Vitodens 200-W B2HE

What the control is telling you

No solar DHW heating; short circuit on the collector temperature sensor. (Manual text for the measures of this code is partly duplicated from the outside sensor entry.)

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Shorted collector sensor or wiring

Test and repair steps

  1. Check the collector sensor and its wiring.
  2. Measure sensor input on the electronics module: about 3.3 V DC with sensor unplugged.
  3. Replace the faulty part.

Models that show this code

4 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-199B2HE-85

Other codes on the same units

  • Connection error Display link lost to HMU
  • F.100 PlusBus voltage error
  • F.104 External fault message input active
  • F.11 Solar collector sensor open circuit
  • F.13 Outside temperature sensor open circuit
  • F.14 Outside temperature sensor short circuit
  • F.142 CAN bus communication error
  • F.143 Fan overheating (air mass flow sensor / recirculation)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.