Viessmann · Boiler

A.18 Possible condensate back-up in heat cell

Medium severity Vitodens 200-W B2HE

What the control is telling you

Warning.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Condensate drain restricted

Test and repair steps

  1. Check combustion chamber and condensate drain; protect electronics from condensate when removing the burner door.
  2. If condensate backed up into the chamber, replace insulation ring, insulation block, insulation mats and ionization electrode.
  3. If condensate reached the flame body, also replace the flame body gasket.

Models that show this code

4 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-199B2HE-85

Other codes on the same units

  • A.12 Real-time clock battery flat
  • A.19 Temperature limiter has responded
  • A.20 Service interval could not be activated
  • Connection error Display link lost to HMU
  • F.100 PlusBus voltage error
  • F.104 External fault message input active
  • F.11 Solar collector sensor open circuit
  • F.12 Solar collector sensor short circuit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.74. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.