Skytech · Gas fireplace
1 Beep Every Second Ignition safety - pilot did not light in 60 seconds
What the control is telling you
The module beeps once a second when it could not light the pilot within 60 seconds.
Applies to: Skytech AF-4000 MOD-1, AF-4000 MOD A and SMART MOD remote modules (used on many fireplace brands)
Likely causes
- Gas supply off
- Module orange/white leads not plugged into the PILOT connection on the valve
- Igniter lead not on the module I terminal
- Flame sensor lead not on the module S terminal
- Black ground lead from the module not on a good ground
- Blocked pilot line
Test and repair steps
- Clear it press OFF, then ON to retry ignition.
- Make sure the gas supply is on.
- Check the orange/white leads from the module are plugged into PILOT on the valve body.
- Check the igniter lead from the pilot assembly is on the module I terminal, and the flame sensor lead is on the S terminal.
- Check the module's black ground lead goes to a proper ground on the fireplace.
- Check the pilot line for blockage.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Skytech Audible Alerts & Error Codes for AF-4000 MOD-1 / MOD A / SMART MOD, p.2-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.