Rinnai · Wall furnace
14 Overheat (fusible link)
What the control is telling you
The overheat safety tripped. The fusible link is a one-time safety device that breaks to shut the furnace off when it overheats.
Applies to: Rinnai EnergySaver direct vent wall furnaces EX08DT, EX11DT, EX17DT, EX22DT
Likely causes
- Dirty air filter restricting airflow
- Underlying overheating condition that must be found
Test and repair steps
- Clean the air filter.
- Turn the furnace off and back on with the ON/OFF button to try to clear the code.
- If it repeats, a qualified service agency must find the cause of the overheat before anything is replaced.
- A blown fusible link may only be replaced by a qualified service agency, after the cause is corrected.
Settings for these units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai EX08DT/EX11DT and EX17DT/EX22DT Installation and Operation Manuals (200000083, 200000084), Table 9 'Diagnostic Codes', p.35–36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.