Rinnai · Wall furnace

11 No ignition

High severity EX DT

What the control is telling you

The burner did not light. Code 11 shows as a dim flashing number. The furnace retries ignition after 1 hour; the code clears after a successful ignition and is not kept in the fault history.

Applies to: Rinnai EnergySaver direct vent wall furnaces EX08DT, EX11DT, EX17DT, EX22DT

Likely causes

  • Gas supply turned off
  • Vent termination blocked
  • Repeated ignition failure needing service

Test and repair steps

  1. Make sure the gas supply to the furnace is ON.
  2. Check that the vent termination outside is not blocked (snow, ice, debris, nests).
  3. The furnace automatically retries ignition after 1 hour (see section 5.7 'Restart Function'). If the flame goes out during forced combustion it also waits 1 hour before retrying.
  4. If the code stays or comes back on the next operation, a trained and qualified technician must service the unit.

Settings for these units

Clearances to combustibles and service · EX DT

LocationClearance
Top0 in. (0 mm)
Bottom / ground0 in. (0 mm)
Front (panel)40 in. (1 m) - flooring or carpet under 1.2 in. (30 mm) high not included
Back (including back spacer)0 in. (0 mm)
Sides (left and right)2 in. (50 mm)
Service access10 in. (254 mm) sides; 40 in. (1 m) front; area above per figure
Exhaust extension pipe1 in. (25.4 mm) to combustibles; 0 in. to non-combustibles

Rinnai recommends 10 in. (254 mm) at top and both sides for servicing.

Service clearance figure above the unit: 10 in. (254 mm) on EX08DT/EX11DT, 9 in. (229 mm) on EX17DT/EX22DT.

Models that show this code

5 models in EX DT

EX08DTEX11DTEX17DTEX22DTEX22DT-W

Other codes on the same units

  • 00 Control mode setting 00 (factory default)
  • 01 Control mode setting 01 (remote thermostat mode)
  • 02 Control mode setting 02 (control panel mode)
  • 14 Overheat (fusible link)
  • 16 Room overheat (above 104°F / 40°C)
  • 30 Overheat temperature thermistor 2 open circuit
  • 31 Room temperature thermistor open circuit
  • 32 Room temperature thermistor short circuit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai EX08DT/EX11DT and EX17DT/EX22DT Installation and Operation Manuals (200000083, 200000084), Table 9 'Diagnostic Codes', p.35–36. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.