Rinnai · Wall furnace
01 Control mode setting 01 (remote thermostat mode)
What the display is showing
Selects remote thermostat mode, for when a wall thermostat kit is installed. Do not select it without the thermostat connection parts installed. The remote thermostat does not turn the furnace on or off, ON/OFF must still be used. Fault codes show on the furnace display, not on the remote thermostat. Unplugging the furnace within two hours of entering this mode sends it back to the factory default.
Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct vent wall furnaces
What to do
- Enter the setting menu as under 00, press Up until 01 shows, then press ON/OFF.
Settings for these units
Clearances to combustibles and service · EX DT
| Location | Clearance |
|---|---|
| Top | 0 in. (0 mm) |
| Bottom / ground | 0 in. (0 mm) |
| Front (panel) | 40 in. (1 m) - flooring or carpet under 1.2 in. (30 mm) high not included |
| Back (including back spacer) | 0 in. (0 mm) |
| Sides (left and right) | 2 in. (50 mm) |
| Service access | 10 in. (254 mm) sides; 40 in. (1 m) front; area above per figure |
| Exhaust extension pipe | 1 in. (25.4 mm) to combustibles; 0 in. to non-combustibles |
Rinnai recommends 10 in. (254 mm) at top and both sides for servicing.
Service clearance figure above the unit: 10 in. (254 mm) on EX08DT/EX11DT, 9 in. (229 mm) on EX17DT/EX22DT.
Models that show this code
5 models in EX DT
Other codes on the same units
- 00 Control mode setting 00 (factory default)
- 02 Control mode setting 02 (control panel mode)
- 11 No ignition
- 14 Overheat (fusible link)
- 16 Room overheat (above 104°F / 40°C)
- 30 Overheat temperature thermistor 2 open circuit
- 31 Room temperature thermistor open circuit
- 32 Room temperature thermistor short circuit
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai EX08DT/EX11DT Installation and Operation Manual (200000083) and EX17DT/EX22DT (200000084), Remote thermostat p.32-33. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.