Rinnai · Wall furnace

00 Control mode setting 00 (factory default)

Menu / mode display EX DT

What the display is showing

Appears when the Economy + Up + Program buttons are held together for 2.5 seconds with the furnace plugged in and off. 00 is the factory default mode.

Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct vent wall furnaces

What to do

  1. Furnace plugged in but OFF, Set back feature OFF.
  2. Hold Economy + Up + Program for 2.5 seconds, then release: 00 shows.
  3. Press Up to move to 01 or 02.
  4. Press ON/OFF; the display goes blank and the mode is stored.

Settings for these units

Clearances to combustibles and service · EX DT

LocationClearance
Top0 in. (0 mm)
Bottom / ground0 in. (0 mm)
Front (panel)40 in. (1 m) - flooring or carpet under 1.2 in. (30 mm) high not included
Back (including back spacer)0 in. (0 mm)
Sides (left and right)2 in. (50 mm)
Service access10 in. (254 mm) sides; 40 in. (1 m) front; area above per figure
Exhaust extension pipe1 in. (25.4 mm) to combustibles; 0 in. to non-combustibles

Rinnai recommends 10 in. (254 mm) at top and both sides for servicing.

Service clearance figure above the unit: 10 in. (254 mm) on EX08DT/EX11DT, 9 in. (229 mm) on EX17DT/EX22DT.

Models that show this code

5 models in EX DT

EX08DTEX11DTEX17DTEX22DTEX22DT-W

Other codes on the same units

  • 01 Control mode setting 01 (remote thermostat mode)
  • 02 Control mode setting 02 (control panel mode)
  • 11 No ignition
  • 14 Overheat (fusible link)
  • 16 Room overheat (above 104°F / 40°C)
  • 30 Overheat temperature thermistor 2 open circuit
  • 31 Room temperature thermistor open circuit
  • 32 Room temperature thermistor short circuit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai EX08DT/EX11DT Installation and Operation Manual (200000083) and EX17DT/EX22DT (200000084), Remote thermostat p.32. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.