Rinnai · Tankless water heater
79 Water leakage detected
What the control is telling you
The internal leak detector has sensed water inside the cabinet, or the leak sensor/its wiring is faulty.
Applies to: Non-SENSEI Series
Likely causes
- Leaking heat exchanger or internal piping
- Water pooled on the cabinet bottom pan
- Wet leak sensor
- Loose, broken or damaged leak detector wiring
- Failed leak sensor
Test and repair steps
- Inspect the leak detector wiring and connections for loose, broken or damaged parts.
- Check the heat exchanger and all internal piping for leaks.
- If no leak is found, look for water pooled on the bottom pan; wipe or blow it out, dry the leak sensor and restart the heater.
- If the cabinet is dry, unplug the sensor and fire the heater; if it runs with the sensor unplugged, replace the sensor and its screw.
Settings for these units
RUCS/RUS unit clearances · Non-SENSEI
| Location | RUCS indoor to combustibles | RUCS indoor to non-combustibles | RUS outdoor to combustibles | RUS outdoor to non-combustibles |
|---|---|---|---|---|
| Top | 6 in. (152 mm) * | 2 in. (51 mm) * | 12 in. (305 mm) | 2 in. (51 mm) |
| Back | 0 in. | 0 in. | 0 in. | 0 in. |
| Front | 6 in. (152 mm) | 6 in. (152 mm) | - | - |
| Front (panel) | - | - | 24 in. (610 mm) | 0 in. |
| Front (exhaust) | - | - | 24 in. (610 mm) | 24 in. (610 mm) |
| Sides | 2 in. (51 mm) | 1/2 in. (13 mm) | 6 in. (152 mm) | 1/8 in. (3.2 mm) |
| Ground/bottom | 12 in. (305 mm) | 12 in. (305 mm) | 12 in. (305 mm) | 2 in. (51 mm) |
| Vent | 0 in. | 0 in. | - | - |
0 in. from vent components and condensate drain line.
Service clearance 24 in. in front of the heater; closet installs need 6 in. (152 mm) in front.
RUCS/RUS water quality limits · Non-SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg / L |
| Aluminum | Up to 0.2 mg / L |
| Chlorides | Up to 250 mg / L |
| Copper | Up to 1.0 mg / L |
| Dissolved CO2 | Up to 15.0 mg / L or PPM |
| Iron | Up to 0.3 mg / L |
| Manganese | Up to 0.05 mg / L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg / L |
| Zinc | Up to 5 mg / L |
Scale build-up shows as code LC# on a controller (LC on the status monitor without one); flush the heat exchanger.
ScaleCutter parts: 103000038 (system), 103000039 (refill).
Models that show this code
67 models in Non-SENSEI, RH180 hybrid
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.62. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.