Rinnai · Tankless water heater
72 Flame rod fault
What the control is telling you
The flame rod circuit is not sensing flame properly, due to wiring, rod position, carbon build-up, low flame current, a heat exchanger leak or a board fault.
Applies to: SENSEI Series, SENSEI RX/CX Series, Non-SENSEI Series
Likely causes
- Broken or damaged flame rod wiring
- Flame rod not contacting the flame
- Carbon build-up on the flame rod
- Flame current below 1 micro amp
- Leaking heat exchanger
- Faulty PC board
Test and repair steps
- Inspect the harness from the flame rods to the PC board for broken or damaged connections.
- Confirm the flame rod sits in the flame when the heater fires.
- Remove the flame rod and look for carbon build-up; replace the rod and gasket if needed.
- Measure flame rod output; it must hold at least 1 micro amp.
- Replace the flame rod and its gasket.
- Check the heat exchanger for leaks and replace it if necessary.
- Replace the PC board.
- SENSEI Transfer data from the old board with the supplied cable, or program all parameters manually per PCB Replacement Instructions (100000553).
- SENSEI RX/CX Transfer data from the old board with the supplied cable, or program all parameters manually per PCB Replacement Instructions (100000854).
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
97 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.60. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.