Rinnai · Tankless water heater

66 Bypass flow servo fault

Medium severity SENSEI RX/CX

What the control is telling you

The bypass flow control device (servo) circuit is faulty on SENSEI RX/CX units.

Applies to: SENSEI RX/CX Series

Likely causes

  • Wet harness or connector
  • Bypass flow control device resistance out of range
  • Failed bypass flow control device
  • Faulty PC board

Test and repair steps

  1. Make sure the harness and connector are dry.
  2. Measure bypass flow control device resistance at PC board connector CN10: red #17–pink #18 = 40-60 Ω; blue #15–white #16 = 40-60 Ω (see Electric Circuit Table/wiring diagram).
  3. Per the manual if either reading is out of range, replace the PC board; otherwise replace the bypass flow control device.

Settings for these units

RX supply connection sizes · SENSEI RX/CX

ConnectionSize
Gas3/4 in. MNPT
Cold inlet3/4 in. MNPT
Hot outlet3/4 in. MNPT
Condensate drain1/2 in. MNPT

Vent connection: 2 in. nominal PVC/CPVC/PP or 3 in./5 in. concentric.

Full specs (input, flow, weight) are only on each model's spec sheet, not in this manual.

RX water quality limits · SENSEI RX/CX

ContaminantMaximum level
Total hardnessUp to 200 mg/L
AluminumUp to 0.2 mg/L
ChloridesUp to 250 mg/L
CopperUp to 1.0 mg/L
Dissolved CO2Up to 15.0 mg/L
IronUp to 0.3 mg/L
ManganeseUp to 0.05 mg/L
pH6.5 to 8.5
TDSUp to 500 mg/L
ZincUp to 5 mg/L

Water damage beyond these limits is not covered by warranty.

Models that show this code

10 models in SENSEI RX/CX

CX160iCX199iCXP160iCXP199iRX130iRX160iRX180iRX199iRXP160iRXP199i

Other codes on the same units

  • 60 Descaling countdown (minutes left)
  • 61 Combustion fan motor fault
  • 63 Recirculation low flow
  • 65 Water flow control device (servo) fault
  • 70 PC board fault
  • 71 Gas solenoid valve fault (SV0–SV4 on Non-SENSEI)
  • 72 Flame rod fault
  • 888 Initial settings saved

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.56. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.