Rinnai · Tankless water heater
65 Water flow control device (servo) fault
What the control is telling you
The water flow control servo is faulty; the servo valve did not close during the bath fill function.
Applies to: SENSEI Series, SENSEI RX/CX Series, Non-SENSEI Series
Likely causes
- Loose, broken or damaged servo wiring
- Water flow control servo failed to close
- Failed water flow control servo
- Incorrect servo resistance or supply voltage at the PC board
Test and repair steps
- Inspect the harness from the water flow servo valve to the PC board for loose, broken or damaged connections.
- Cycle power off and on and see whether the code clears.
- Because the servo failed to close during bath fill, shut off the water flow right away and stop using the bath fill controller.
- Warning: Turn off the electrical, gas and water supply to the heater before continuing.
- Replace the water flow control servo.
- SENSEI At connector D: red #18–pink #20 = 44–52 Ω; white #16–blue #14 = 44–52 Ω; grey #30 (black near the board)–orange #12 = 12–14 VDC.
- SENSEI RX/CX At CN9: red #16–pink #17 and white #15–blue #14 = 40-60 Ω; grey #5–orange #9 = 11-13 VDC; grey #5–brown #13 = under 1 VDC with limiter on, 4-6 VDC with limiter off.
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
97 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.55. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.