Rinnai · Tankless water heater

58 Secondary heat exchanger bi-metal switch open

High severity Non-SENSEIRH180 hybrid

What the control is telling you

One of the two bi-metal switches at the rear of the secondary heat exchanger (where the air box joins it) has opened. Shows even when idle; fix the cause, then cycle power (hard reset).

Applies to: Non-SENSEI Series

Likely causes

  • Scale build-up inside the secondary heat exchanger
  • Untreated hard water supply
  • Loose, broken or damaged sensor wiring
  • Open bi-metal switch circuit

Test and repair steps

  1. Inspect the sensor harness from the secondary HX bi-metal switches to the PC board for loose, broken or damaged connections.
  2. Measure the circuit resistance at the PC board connectors; it should be under 1 ohm.
  3. This code points to scale inside the secondary heat exchanger: flush it per the owner's manual to prevent damage.
  4. Treat hard water to stop scale from forming and damaging the heat exchanger.
  5. After the problem is corrected, hard reset by turning power off and back on.

Settings for these units

RUCS/RUS unit clearances · Non-SENSEI

LocationRUCS indoor to combustiblesRUCS indoor to non-combustiblesRUS outdoor to combustiblesRUS outdoor to non-combustibles
Top6 in. (152 mm) *2 in. (51 mm) *12 in. (305 mm)2 in. (51 mm)
Back0 in.0 in.0 in.0 in.
Front6 in. (152 mm)6 in. (152 mm)--
Front (panel)--24 in. (610 mm)0 in.
Front (exhaust)--24 in. (610 mm)24 in. (610 mm)
Sides2 in. (51 mm)1/2 in. (13 mm)6 in. (152 mm)1/8 in. (3.2 mm)
Ground/bottom12 in. (305 mm)12 in. (305 mm)12 in. (305 mm)2 in. (51 mm)
Vent0 in.0 in.--

0 in. from vent components and condensate drain line.

Service clearance 24 in. in front of the heater; closet installs need 6 in. (152 mm) in front.

RUCS/RUS water quality limits · Non-SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg / L
AluminumUp to 0.2 mg / L
ChloridesUp to 250 mg / L
CopperUp to 1.0 mg / L
Dissolved CO2Up to 15.0 mg / L or PPM
IronUp to 0.3 mg / L
ManganeseUp to 0.05 mg / L
pH6.5 to 8.5
TDSUp to 500 mg / L
ZincUp to 5 mg / L

Scale build-up shows as code LC# on a controller (LC on the status monitor without one); flush the heat exchanger.

ScaleCutter parts: 103000038 (system), 103000039 (refill).

Models that show this code

67 models in Non-SENSEI, RH180 hybrid

C199eC199iR50LSiR63LSe2R75LSeR75LSiR94LSeR94LSiR98LSeR98LSe-ASMER98LSiR98LSi-ASMERC80eRC80iRC98eRC98iRE140eRE140iRE160eRE160iRE180eRE180iRE199eRE199iREP160eREP160iREP199eREP199iRH180RL75eRL75e(A)RL75iRL75i(A)RL94eRL94iRLX94iRU80eRU80iRU90eRU98eRU98iRUC80iRUC90iRUC98iRUCS65iRUCS75iRUR98eRUR98iRUS65eRUS75eV53DeV53eV65eV65iV75eV75iV94XiV94eV94iVE140e

Other codes on the same units

  • 41 Freeze protection / outdoor air temperature sensor fault
  • 51 Inlet water temperature thermistor fault
  • 52 Gas valve / modulating solenoid valve (POV) signal fault
  • 54 High exhaust gas temperature
  • 57 Burner overheat bi-metal switch open
  • 61 Combustion fan motor fault
  • 63 Recirculation low flow
  • 65 Water flow control device (servo) fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.51. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.