Rinnai · Boiler

363 CH return thermistor fault

Medium severity I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the control is telling you

Fault detected in the return thermistor, which relates to central heating only.

Applies to: I-Series Plus boilers — 150K BTU and smaller and 175K BTU and higher (Combi and Solo)

Likely causes

  • Loose, broken or damaged thermistor wiring/connectors
  • Thermistor unplugged (reads -40)
  • Scale or deposits on the thermistor
  • Failed thermistor (resistance out of range)
  • Faulty PC Board

Test and repair steps

  1. Inspect the thermistor harness from the sensor back to the PC Board for loose, broken or damaged connections.
  2. Caution shut off the water supply and drain the system down before going further.
  3. Open Performance Data 04 and compare the displayed temperature with a thermometer at the same spot. Within 5° = sensor OK; more than 5° off = continue; a reading of -40 means unplugged or poor connection.
  4. With the lines drained/isolated, pull the thermistor and clean off any scale or deposits.
  5. Measure resistance on a 20K ohm range; it should drop when warmed by hand and rise on ice. 150K and smaller: CN7 pins 8 and 10. 175K and higher: CN7 pins 8 and 10.
  6. Compare readings against Appendix A Water Temperatures in the source manual (p.22 references it); replace the sensor if it is off by more than 5°F.
  7. Cross-check the readings with the controller's performance data; if correct, reinstall the thermistor with its small O-ring intact and lightly lubricated.
  8. Restore water/power and check for leaks around the thermistor.
  9. Fire the unit again; if code 363 persists, replace the thermistor.
  10. If the code returns after a new thermistor, replace the PC Board.

Models that show this code

6 models in I-Series Plus 150K and smaller, I-Series Plus 175K and higher

IP060SIP090SIP120SIP150SIP175SIP199S

Other codes on the same units

  • 303 Secondary system thermistor fault
  • 310 Freeze protection thermistor fault
  • 353 CH supply thermistor fault
  • 371 Indirect tank thermistor fault
  • 380 Exhaust thermistor fault
  • 393 Outdoor temperature sensor fault
  • 400 Water pressure sensor communication fault
  • 430 High or low system water pressure

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.22. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.