Rinnai · Boiler

380 Exhaust thermistor fault

Medium severity I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the control is telling you

Fault detected in the exhaust temperature thermistor in the exhaust duct housing.

Applies to: I-Series Plus boilers — 150K BTU and smaller and 175K BTU and higher (Combi and Solo)

Likely causes

  • Loose, broken or damaged thermistor wiring
  • Thermistor unplugged (reads -40)
  • Failed exhaust or return thermistor
  • Wrong gas type, orifice or A0 setting
  • Poor clearances at unit/vent termination
  • Clogged heat exchanger fins

Test and repair steps

  1. Inspect the thermistor harness from the sensor back to the PC Board for loose, broken or damaged connections.
  2. Open Performance Data 06 and compare the exhaust temperature with a thermometer at the same spot. Within 5° = OK; more than 5° off = continue; -40 = unplugged or poor connection.
  3. Remove the thermistor from the exhaust duct housing.
  4. Measure it on a 20K ohm range; resistance should drop when warmed by hand and rise against ice. 150K and smaller: CN7 pins 3 and 6. 175K and higher: CN7 pins 3 and 14.
  5. Compare against Appendix B Exhaust Temperatures in the source manual; replace if more than 5°F off.
  6. Also check the return thermistor resistance (same values as the exhaust thermistor).
  7. Confirm the gas supply matches the rating plate and the gas valve has the right orifice (black = NG, grey = LPG, white = NG high altitude above 2000 ft).
  8. Confirm Parameter A0 matches the supplied gas (A = Natural Gas, b = Propane).
  9. Confirm proper clearances around the unit and vent termination.
  10. If heat exchanger fins are clogged, clean with 120 psi compressed air or replace the heat exchanger.

Models that show this code

6 models in I-Series Plus 150K and smaller, I-Series Plus 175K and higher

IP060SIP090SIP120SIP150SIP175SIP199S

Other codes on the same units

  • 353 CH supply thermistor fault
  • 363 CH return thermistor fault
  • 371 Indirect tank thermistor fault
  • 393 Outdoor temperature sensor fault
  • 400 Water pressure sensor communication fault
  • 430 High or low system water pressure
  • 443 Low water cut-off (LWCO) activated
  • 520 Gas solenoid valve circuit – flame after valve close

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.